Molded Case Circuit Breaker 50441

R13386,09

closed toroid A type, for VigiPacT and Vigilhom, SA200, inner diameter 200 mm, rated current 400 A

Description

This toroid is dedicated to Vigilohm Insulation Fault locators, and to VigiPacT type A residual current protection and monitoring relays. It allows the monitoring of the injected component from Vigilohm Insulation Monitor, and the measurement of a current rating up to 400A for VigiPacT monitoring and protection relays. The transformer ratio is 1/1000. The inner diameter of the toroid is 200 millimeters and the weight is 1.320kg. The cables must be centered within the toroid and the diameter represented by all these cables should not exceed 100 millimeters. The maximum cross section per phase (R, S, T, N) is 2 cables of 185mm? for a copper conductor.

Additional information

Weight 1,100 kg
Dimensions 28,400 × 27,000 × 7,500 cm